Search results

1 – 10 of 30
Article
Publication date: 1 January 2014

Mohammadreza Barzegaran and Osama A. Mohammed

– In this paper, modeling of the XLPE cable for electromagnetic signature study at a far distance is proposed. The paper aims to discuss these issues.

Abstract

Purpose

In this paper, modeling of the XLPE cable for electromagnetic signature study at a far distance is proposed. The paper aims to discuss these issues.

Design/methodology/approach

Due to the very small ratio of the dimensions of cables to the dimensions of the whole system, using actual geometry of the cables with all layers in this study causes deformation of the cable's model. Therefore, multi-dipole modeling is used for modeling the cables.

Findings

This model includes specific voltages and currents in lines and nodes, respectively. Radiated electric and magnetic fields at a far distance are selected as the index of appropriateness of the model.

Originality/value

In order to investigate the accuracy of the model, various configuration of the cable is studied. Additionally, coupling of the cable with an electrical machine is investigated. They all show that the equivalent models can be used in place of the actual model for signature studies.

Details

COMPEL: The International Journal for Computation and Mathematics in Electrical and Electronic Engineering, vol. 33 no. 1/2
Type: Research Article
ISSN: 0332-1649

Keywords

Article
Publication date: 2 March 2012

Min‐You Chen, Jin‐qian Zhai, Z.Q. Lang, Feng Sun and Gang Hu

The present study is concerned with the application of a nonlinear frequency analysis approach to the detection and location of water tree degradation of power cable XLPE

Abstract

Purpose

The present study is concerned with the application of a nonlinear frequency analysis approach to the detection and location of water tree degradation of power cable XLPE insulation without turning off electric power.

Design/methodology/approach

The use of power cable system responses to power line carrier signals are proposed to conduct the required signal analysis for damage location purpose. This technique is based on the fact that the water tree degradation in power cables can make the system behave nonlinearly. Consequently, the location of water tree degradation can be determined by detecting the position of nonlinear components in power cable systems.

Findings

A novel method has been proposed for locating water tree degradation in power cable systems; numerical simulation studies have demonstrated the effectiveness of the new technique.

Originality/value

The proposed technique has the potential to be applied in practice to more effectively resolve the power cable damage location problem.

Details

COMPEL - The international journal for computation and mathematics in electrical and electronic engineering, vol. 31 no. 2
Type: Research Article
ISSN: 0332-1649

Keywords

Article
Publication date: 7 September 2015

Anwar Ul-Hamid, Khaled Y. Soufi, Luai M. Al-Hadhrami and Ahsan M. Shemsi

– This paper aims to determine the effect of exposure of underground electrical cables to chemically contaminated water.

Abstract

Purpose

This paper aims to determine the effect of exposure of underground electrical cables to chemically contaminated water.

Design/methodology/approach

Visual inspection and photography were carried out to record the appearance of electrical cables. Failed and un-failed cable samples were collected and analyzed using light microscopy, scanning electron microscopy coupled with energy-dispersive X-ray spectroscopy and Fourier transform infrared spectroscopy. Sand and water samples were chemically tested for contaminants.

Findings

Underground low-voltage 0.6/1-kV cross-linked polyethene insulated cables belonging to a chemical production plant suffered failure after four years of service. Excavation of the cable trench revealed that the cables were buried in sand polluted with chemically contaminated water. The cables were discolored and covered with corrosion deposits. Experimental results indicated that the cable insulation was heavily degraded and the outer jacket of polyvinyl chloride exhibited cracks that had penetrated through its thickness. Water and sand surrounding the cable were found to have high concentrations of ammonia. Mechanical testing of the cables indicated high values of stiffness that could contribute to the formation of cracks at the surface.

Practical implications

It was concluded that contamination in the water had degraded the cable, resulting in the development of a network of branched cracks within the cable insulation through which water could permeate, leading to eventual failure of the cable. Accelerated degradation took place due to exposure to the contaminated environment, which promoted aging and brittleness. Continued exposure of electric cables to contamination would lead to power failures and plant shutdowns.

Originality/value

This paper provides an account of a failure investigation of low-voltage electrical cable buried underground. It discusses the role of contaminated environment in the eventual failure of electrical cable due to corrosion. This information will be useful for plant engineers and project managers working in any industry that makes use of chemicals.

Details

Anti-Corrosion Methods and Materials, vol. 62 no. 5
Type: Research Article
ISSN: 0003-5599

Keywords

Article
Publication date: 2 January 2018

Ruchi Mishra

The purpose of this paper is to explore different drivers and volume flexibility strategies employed in manufacturing firms. It also examines contingent factors, which determine…

Abstract

Purpose

The purpose of this paper is to explore different drivers and volume flexibility strategies employed in manufacturing firms. It also examines contingent factors, which determine volume flexibility requirement in manufacturing firms.

Design/methodology/approach

Using a multi-case study approach, the study examines and analyses drivers, strategies and contingent factors that affect volume flexibility in four Indian manufacturing plants belonging to automobiles, auto ancillary, fashion apparel and electrical industry.

Findings

The empirical analysis suggests various drivers of volume flexibility and different strategies employed by firms to enhance flexibility. The study also illustrates various contingent factors that determine the need of volume flexibility in firms.

Research limitations/implications

The sample of the study is majorly confined to the northern region of India. Methodologically, the analysis is solely based on the qualitative data.

Practical implications

The study suggests practitioners to consider a range of contingent factors, while evaluating the need of volume flexibility in manufacturing plants. Rather than relying on a single strategy, a mix of strategies should be used to develop volume flexibility in firms.

Originality/value

The identification of a range of strategies employed by volume flexible firms as well as contingent factors that need to be evaluated before employing volume flexibility are the major contributions of this study.

Details

International Journal of Quality & Reliability Management, vol. 35 no. 1
Type: Research Article
ISSN: 0265-671X

Keywords

Article
Publication date: 21 January 2022

Christoph Jörgens and Markus Clemens

In high voltage direct current cable systems, cable joints are known as the least reliable components due to the use of multiple dielectrics. Resulting from the electric field and…

Abstract

Purpose

In high voltage direct current cable systems, cable joints are known as the least reliable components due to the use of multiple dielectrics. Resulting from the electric field and temperature depending conductivity of the different dielectrics, field enhancement at critical areas, e.g. triple points, may result in accelerated aging and the failure of the component. To reduce the stress, different field grading techniques are applied. The purpose of this study is to investigate different grading techniques for cable joints. Different shapes of the electrode and a varying nonlinear conductivity of field grading materials (FGM) are used for the simulation of the electric field.

Design/methodology/approach

Coupled electro-thermal field simulations are applied for different joint geometries, to obtain the stationary electric field. Electric field simulations in cable joint using geometric and nonlinear field grading techniques are shown.

Findings

Using the geometric field grading, the shape of the stress cone determines the field values in critical areas (triple points). High stress reduction is obtained for a certain curvature of the stress cone. For the nonlinear stress control, materials with a higher conductivity in comparison to the cable and the joint material are used. A field reduction is obtained by increasing the total conductivity. On the other hand, this is also increasing the insulation losses within the total FGM. More applicable is the decrease of the switching field or the increase of nonlinearity, which is only locally increase the conductivity and the insulation losses. Furthermore, simulations results show that an approximately constant field reduction is obtained, if the nonlinearity is above a certain threshold.

Research limitations/implications

This study is restricted to a field dependency of FGM only. For impulse voltages, high temperature and electric conductivity values my result in a thermal runaway. Furthermore, only direct current field grading techniques are studied.

Originality/value

The field grading of cable joints, using geometric and nonlinear techniques, is analyzed. A comparison between the electric field, by varying the curvature of the ground stress cone or the FGM conductivity constants in a complex joint geometry is novel. With its effect on the electric fields, general requirements for the geometry (geometric field grading) or the values of the FGM constants (nonlinear field grading) are defined to obtain a sufficient field grading.

Details

COMPEL - The international journal for computation and mathematics in electrical and electronic engineering , vol. 41 no. 4
Type: Research Article
ISSN: 0332-1649

Keywords

Article
Publication date: 8 May 2018

Miao He, Miao Hao, George Chen, Wenpeng Li, Chong Zhang, Xin Chen, Haitian Wang, Mingyu Zhou and Xianzhang Lei

For the dramatically developed high voltage direct current (HVDC) power transmission, HVDC cables play a vital role in the power transmission across seas and connections with…

Abstract

Purpose

For the dramatically developed high voltage direct current (HVDC) power transmission, HVDC cables play a vital role in the power transmission across seas and connections with renewable power sources. However, the condition monitoring of HVDC cables is still a challenging research topic. This paper aims to understand the influence of external factors, namely, current, cavity location and material properties, on partial discharge (PD) characteristics in HVDC cable in a numerical way referring to the refined Niemeyer’s model.

Design/methodology/approach

The influences of the three external factors are studied by a proposed numerical model for DC PDs based on the modification of a conventional PD model for AC voltage via a finite element analysis method.

Findings

The external factors can influence the discharge magnitude and discharge repetition rate via affecting the electrical conductivity of the material: DC PD is more frequent and with higher discharge magnitude when the cavity is closer to the conductor or the current through the conductor is higher. Both DC PD repetition rate and average discharge magnitude in long-term aged material are lower than virgin material. The effect of discharge on insulation degradation becomes decreasingly significant.

Research limitations/implications

The current work is based on the numerical modelling of DC PDs. Further experimental validations and comparisons are essential for improving the model.

Practical implications

The studies of the influence factors for PDs under HVDC voltage can benefit the research and practical power transmission on DC PDs, contributing the design and test of DC PDs in HVDC cables, exploring the understandings of the DC PDs’ mechanism.

Originality/value

This paper, to the best of author’s knowledge, first studies the influence factors on DC PDs based on the numerical modelling work.

Details

COMPEL - The international journal for computation and mathematics in electrical and electronic engineering, vol. 37 no. 3
Type: Research Article
ISSN: 0332-1649

Keywords

Article
Publication date: 20 August 2018

Christoph Jörgens and Markus Clemens

In high voltage direct current (HVDC), power cables heat is generated inside the conductor and the insulation during operation. A higher amount of the generated heat in comparison…

Abstract

Purpose

In high voltage direct current (HVDC), power cables heat is generated inside the conductor and the insulation during operation. A higher amount of the generated heat in comparison to the dissipated one, results in a possible thermal breakdown. The accumulation of space charges inside the insulation results in an electric field that contributes to the geometric electric field, which comes from the applied voltage. The total electric field decreases in the vicinity of the conductor, while it increases near the sheath, causing a possible change of the breakdown voltage.

Design/methodology/approach

Here, the thermal breakdown is studied, also incorporating the presence of space charges. For a developed electro-thermal HVDC cable model, at different temperatures, the breakdown voltage is computed through numerical simulations.

Findings

The simulation results show a dependence of the breakdown voltage on the temperature at the location of the sheath. The results also show only limited influence of the space charges on the breakdown voltage.

Research limitations/implications

The study is restricted to one-dimensional problems, using radial symmetry of the cable, and does not include any aging or long-term effect of space charges. Such aging effect can locally increase the electric field, resulting in a reduced breakdown voltage.

Originality/value

A comparison of the breakdown voltage with and without space charges is novel. The chosen approach allows for the first time to assess the influence of space charges and field inversion on the thermal breakdown.

Details

COMPEL - The international journal for computation and mathematics in electrical and electronic engineering, vol. 37 no. 5
Type: Research Article
ISSN: 0332-1649

Keywords

Article
Publication date: 5 March 2018

Miao He, Miao Hao, George Chen, Xin Chen, Wenpeng Li, Chong Zhang, Haitian Wang, Mingyu Zhou and Xianzhang Lei

High voltage direct current (HVDC) cable is an important part in the electric power transmission and distribution systems. However, very little research has been carried out on…

Abstract

Purpose

High voltage direct current (HVDC) cable is an important part in the electric power transmission and distribution systems. However, very little research has been carried out on partial discharge under direct current (DC) conditions. Niemeyer’s model has been widely used under alternating current (AC) conditions. This paper aims to intend to modify the Niemeyer’s model considering both electric field and charge dynamics under DC conditions, and therefore proposes a numerical model describing partial discharge characteristics in HVDC cable.

Design/methodology/approach

This paper intends to understand partial discharge characteristics under DC conditions through numerical modelling. Niemeyer’s model that has been widely used under AC conditions has been modified, taking both electric field and charge dynamics under DC conditions into consideration. The effects of loading level or current through the conductor, cavity location and material properties on partial discharges have also been studied.

Findings

Electrical conductivity is important in determining the characteristics of partial discharge under DC conditions and discharges tend to happen in short when the cavity field exceeds the inception level under the parameter values studied in the paper.

Research limitations/implications

Building the numerical model is the purpose of the paper, and there is lack in experiment and the comparison between the simulation results and experiment.

Practical implications

The proposed model provides the numerical model describing partial discharge in HVDC cable and helps understand the partial discharge mechanism under DC voltage.

Originality/value

To the best of the author’s knowledge, this paper is a very early research on the numerical modelling work on partial discharge under DC voltage.

Details

COMPEL - The international journal for computation and mathematics in electrical and electronic engineering, vol. 37 no. 2
Type: Research Article
ISSN: 0332-1649

Keywords

Article
Publication date: 31 July 2023

Chong Xu, Pengbo Wang, Fan Yang, Shaohua Wang, Junping Cao and Xin Wang

This paper aims at building a discharge model for the power cable bellows based on plasma energy deposition and analyzing the discharge ablation problem.

Abstract

Purpose

This paper aims at building a discharge model for the power cable bellows based on plasma energy deposition and analyzing the discharge ablation problem.

Design/methodology/approach

Aiming at the multiphysical mechanism of the discharge ablation process, a multiphysical field model based on plasma energy deposition is established to analyze the discharge characteristics of the power cable bellows. The electrostatic field, plasma characteristics, energy deposition and temperature field are analyzed. The discharge experiment is also carried out for result validation.

Findings

The physical mechanism of the bellows ablative effect caused by partial discharge is studied. The results show that the electric field intensity between the aluminum sheath and the buffer layer easily exceeds the pressure resistance value of air breakdown. On the plasma surface of the buffer layer, the electron density is about 4 × 1,019/m3, and the average temperature of electrons is about 3.5 eV. The energy deposition analysis using the Monte Carlo method shows that the electron range in the plasma is very short. The release will complete within 10 nm, and it only takes 0.1 s to increase the maximum temperature of the buffer layer to more than 1,000 K, thus causing various thermal effects.

Originality/value

Its physical process involves the distortion of electric field, formation of plasma, energy deposition of electrons, and abrupt change of temperature field.

Details

COMPEL - The international journal for computation and mathematics in electrical and electronic engineering , vol. 42 no. 6
Type: Research Article
ISSN: 0332-1649

Keywords

Article
Publication date: 17 March 2016

Zhengyi Han, George Chen, Junzheng Cao, Zhiyuan He, Haitian Wang, Wenpeng Li and Chao Tang

The pulsed electro-acoustic (PEA) method is widely applied for space charge measurement in solid dielectrics. The signals, however, can be seriously distorted during transmission…

Abstract

Purpose

The pulsed electro-acoustic (PEA) method is widely applied for space charge measurement in solid dielectrics. The signals, however, can be seriously distorted during transmission, especially in non-planar specimens. The aim of this work is to find an efficient algorithm to correctly recover the space charge profile for different types of specimens.

Design/methodology/approach

The distortion can be associated with both geometry and material (attenuation and dispersion). Hence the recovery algorithm consists of two parts respectively. The influences of geometries, causing the divergences of electric force and acoustic waveform, can be corrected by sets of factors. The attenuation and dispersion of the material can be suppressed based on the transfer function matrix in frequency domain, which could be obtained from calibration.

Findings

A general algorithm applicable to three kinds of specimens (single-layer, multi-layer and coaxial-geometry dielectrics) has been proposed. Compared with the other two algorithms in literature, the present one offers the most accurate solution while taking relatively shorter time. In addition, this algorithm is applied on signals measured from a planar LDPE sample and the results show that the new algorithm is fairly effective with excellent stability in a real system.

Originality/value

As one of the most accurate algorithms, the present one is theoretically one third quicker than the others. This algorithm would be helpful in applications calling for large calculations, i.e. 3-D imaging of space charge distribution in XLPE cable.

Details

COMPEL - The international journal for computation and mathematics in electrical and electronic engineering , vol. 35 no. 3
Type: Research Article
ISSN: 0332-1649

1 – 10 of 30