Search results

1 – 1 of 1
Article
Publication date: 28 May 2020

András Jakab, Viktor Hlavicka, Ágoston Restás and Eva Lubloy

During the building designing, it is very important to deal with the fire resistance of the structures. The designed materials for escape routes should be selected to ensure the…

Abstract

Purpose

During the building designing, it is very important to deal with the fire resistance of the structures. The designed materials for escape routes should be selected to ensure the usability of the structures until the time of escape. Planning affects the glass structures similarly, so these can also be partition walls and load bearing structures, although the latter is less applied on escape routes. The heat protection of the glasses can be improved with heat-protective foils, while fire protection is provided by gel intumescent material.

Design/methodology/approach

To research the topic of fire resistance, laboratory experiments were carried out on small-scaled glass elements with thermal protection foil at Budapest University of Technology and Economics at the Department of Construction Materials and Technologies.

Findings

Fire protection of small model specimens was tested with blowtorch fire and furnace heat load. During the experiments, six foils were tested. Single pane glass, double layered and triple glazed specimens were tested with blowtorch fire.

Originality/value

Fire protection of small model specimens was tested with blowtorch fire and furnace heat load. During the experiments, six foils were tested. Single pane glass, double layered and triple glazed specimens were tested with blowtorch fire. In case of heat-protected glazing, the foils on the “protected” side of the single pane glass do not have a fire protection effect based on blowtorch fire test. For double glassed specimens, the P35 foil has a perceptible effect, even for the requirements of the flame breakthrough (E, integrity), when the foil is placed on the inner side (position 3) of the second glass layer. The stratification of each triple glazed specimens was effective against blowtorch fire load (3 M, S4&P35), so (EI, integrity and isolation) it can meet the requirements of flame breakthrough and thermal insulation.