Search results

1 – 2 of 2
Article
Publication date: 15 February 2024

Yumin He, Tingyun Gu, Bowen Li, Yu Wang, Dongyuan Qiu, Yang Zhang and Peicheng Qiu

Electric spring (ES) is a demand response method that can stabilize the voltage of critical loads and improve power quality, especially in a weak power grid with a high proportion…

Abstract

Purpose

Electric spring (ES) is a demand response method that can stabilize the voltage of critical loads and improve power quality, especially in a weak power grid with a high proportion of renewable energy sources. Most of existing ESs are implemented by voltage-source inverter (VSI), which has some shortcomings. For example, the DC-link capacitor limits the service life of ES, and the battery is costly and hard to recycle. Besides, conventional VSI cannot boost the voltage, which limits the application of ES in high-voltage occasions. This study aims to propose a novel scheme of ES to solve the above problems.

Design/methodology/approach

In this work, an ES topology based on current-source inverter (CSI) without a battery is presented, and a direct current control strategy is proposed. The operating principles, voltage regulation range and parameter design of the proposed ES are discussed in detail.

Findings

The proposed ES is applicable to various voltage levels, and the harmonics are effectively suppressed, which have been validated via the experimental results in both ideal and distorted grid conditions.

Originality/value

An ES topology based on battery-less CSI is proposed for the first time, which reduces the cost and prolongs the service time of ES. A novel control strategy is proposed to realize the functions of voltage regulation and harmonic suppression.

Details

COMPEL - The international journal for computation and mathematics in electrical and electronic engineering , vol. 43 no. 1
Type: Research Article
ISSN: 0332-1649

Keywords

Article
Publication date: 30 March 2022

Karthick R., Ramakrishnan C. and Sridhar S.

This paper aims to introduce the quasi impedance source inverter (qZSI)-based static compensator (STATCOM), which is incorporated into the hybrid distributed power generation…

Abstract

Purpose

This paper aims to introduce the quasi impedance source inverter (qZSI)-based static compensator (STATCOM), which is incorporated into the hybrid distributed power generation system for enhancement of power quality. The distributed power generation system includes the photovoltaic (PV), wind energy conversion system (WECS) and battery energy storage system.

Design/methodology/approach

The WECS is used by the self-excited induction generator (SEIG) and the flywheel energy storage system (FESS). To regulate its terminal voltage and frequency, the SEIG requires adjustable volt-ampere reactive (VAR). A combination of a STATCOM and a fixed condenser bank usually serves to satisfy the VAR demand. The maximum correntropy criterion-based adaptive filter technique (AFT) is proposed to control the qZSI-STATCOM and to guarantee that the voltage at the SEIG terminal is harmonic-free while providing non-linear three-phase and single-phase loads.

Findings

The coordinated operation of the suggested voltage control and flywheel control systems ensures that load voltage and frequency are retained in their respective values at very low harmonic distortions regardless of wind speed and load variation. The simulation and experimental studies are carried out under different load conditions to validate the efficiencies of the PV-assisted STATCOM.

Originality/value

To improve system stability and minimize total costs, extra load current sensors can also be avoided. This paper proposes to control the SEIG terminal voltage and harmonic elimination in the standalone WECS systems using maximum correntropy criterion-based AFT with a fuzzy logic controller.

Access

Year

Last 12 months (2)

Content type