This study aims to focus on the grid connected inverter.

Abstract

Purpose

This study aims to focus on the grid connected inverter.

Design/methodology/approach

The grid connected inverter for harmonic suppression was designed, the topological structure of the inverter and the design of LCL filter were analyzed, then a PIR controller was proposed and finally simulation and experiment were carried out.

Findings

The simulation results showed that the distortion rates of the 5th, 7th and 11th harmonics under PIR control were 0.14%, 0.13% and 0.06%, respectively, which were significantly lower than that under PI control. The system test results also showed that the current waveform under PI control was rough and total harmonic distortion (THD) content was 3.8%; under PIR control, the grid connected current waveform was relatively smooth, with fewer spikes and burrs, and the THD content was 1.9%, indicating that the harmonics were effectively suppressed.

Originality/value

The experimental results verify that the inverter and PIR controller designed in this study are effective for harmonic suppression. This work makes some contributions to the improvement of the effect of harmonic suppression and promotion of the better application of grid connected inverter.