Search results

1 – 10 of 12
Article
Publication date: 3 October 2016

Stephen Loh Tangwe, Michael Simon and Edson L. Meyer

This paper aims to show that by using air source heat pump (ASHP) water heater in the residential sector, the energy consumption from sanitary hot water production can be reduced…

Abstract

Purpose

This paper aims to show that by using air source heat pump (ASHP) water heater in the residential sector, the energy consumption from sanitary hot water production can be reduced by more than 50 per cent. Hence, this study quantitatively and qualitatively confirms that domestic ASHP water heater is a renewable and energy efficient device for sanitary hot water production.

Design/methodology/approach

Design and building of a data acquisition system comprises a data logger, power meters, flow meters, temperature sensors, ambient and relative humidity sensor and an electronic input pulse adapter to monitor the ASHP water heater performance. All the sensors are accommodated by the U30-NRC data logger. The temperature sensors are installed on the inlet pipe containing a flow meter and the outlet pipe of the ASHP unit, the vicinity of both evaporator and expel cold air. An additional temperature sensor and a flow meter that cater for hot water drawn off measurements are incorporated into the data acquisition system (DAS).

Findings

The result from a specific monitoring split type ASHP water heater gives an average daily coefficient of performance (COP) of 2.36 and the total electrical energy of 4.15 kWh, and volume of hot water drawn off was 273 L. These results were influenced by ambient temperature and relative humidity.

Research limitations/implications

The cost involved in purchasing the entire sensors and data logger limits the number and categories of ASHP water heaters whose performance were going to be monitored. Pressure sensors were excluded in the data acquisition system.

Practical implications

The data acquisition system can easily be designed and the logger can also be easily programed. Hence, no high technical or computer skills are needed to install the DAS and to be able to read out the results.

Social implications

Hence, the data acquisition system can be installed on the entire domestic Eskom roll out air source heat pump water heaters to effectively determine the coefficient of performance and demand reductions.

Originality/value

This DAS is the first of its kind to be built in South Africa to be used to determine the performance of an ASHP water heater with high accuracy and precision. DAS is also robust.

Details

Journal of Engineering, Design and Technology, vol. 14 no. 4
Type: Research Article
ISSN: 1726-0531

Keywords

Article
Publication date: 21 January 2019

Stephen loh Tangwe and Michael Simon

This paper aims to compute demand, consumption and other avoidance saving by replacing existing geysers with split and integrated type air source heat pump (ASHP) water heaters…

Abstract

Purpose

This paper aims to compute demand, consumption and other avoidance saving by replacing existing geysers with split and integrated type air source heat pump (ASHP) water heaters, to prove the potential of both ASHP water heaters in both winter and summer by virtue of their coefficient of performance (COP) during the vapour compression refrigeration cycles and to demonstrate that despite the viability of both split and integrated ASHP system, the latter exhibits a better performance in terms of its COP and achievable savings and load factor.

Design/methodology/approach

This research emphasised the use of the data acquisition system housing various temperature sensors, power metres, flow metre, ambient temperature and relative humidity sensor to determine electrical energy consumption and useful thermal energy gained by the hot water in a geyser and storage tanks of residential ASHP water heaters. The load factors, average power and electrical energy consumptions for the 150 L high-pressure geyser, a 150 L split and integrated type ASHP water heaters were evaluated based on the controlled volume (150, 50 and 100 L) of daily hot water drawn off.

Findings

The results depicted that the average electrical energy consumed and load factors of the summer months for the geyser, split and integrated type ASHP water heaters were 312.3, 111.7 and 121.1 kWh and 17.9, 10.2 and 16.7 per cent, respectively. Finally, the simple payback period for both the split and integrated type ASHP water heaters were determined to be 3.9 and 5.2 years, respectively. By the application of the Eskom’s projected tariff hikes over the years, the payback periods for the split and integrated ASHP water heaters could be reduced to 3.3 and 4.1 years, respectively.

Research limitations/implications

The experiments were conducted in a controlled outdoor research facility as it was going to be of great challenge in conducting both experiments simultaneously in a specific home. The category of the different types of ASHP water heaters was limited to one due to the cost implication. The experiment was also conducted at a single location, which is not a full representation of all the ambient conditions of the different regions of South Africa.

Practical implications

The experiments were done with a specific controlled volume of hot water drawn off from each of the three hot water heating devices. The experiments was structuring controlled to a specific volume of hot water drawn off and at specific period of the day and hence to not cater for random drawers and intermittent drawn off.

Social implications

The findings help to assure homeowners that irrespective of the type of ASHP water heaters installed in their residence, they can be guarantee of year-round performance and a favourable payback period provided their hot water consumption is over 200 L per day. Also, although the split type ASHP water heater performed better than the integrated system the cost of installation and maintenance will be higher in a split type in comparison to the integrated type. Finally, by successful implementation of either of the ASHP water heaters the home owner can substantially save of his hot water bill.

Originality/value

The experimental design and methodology is the first of its kind to be conducted in South Africa. The results and interpretation were obtained from original data collected from the set of experiments conducted. Also, the authors are able to show that the introduction of back up element in an ASHP unit to run simultaneously with the vapour compression refrigeration cycles of the ASHP can reduce the COP of the overall system.

Details

Journal of Engineering, Design and Technology, vol. 17 no. 2
Type: Research Article
ISSN: 1726-0531

Keywords

Article
Publication date: 5 June 2017

Stephen Loh Tangwe, Michael Simon and Edson Leroy Meyer

The purpose of this study was to build and develop mathematical models correlating ambient conditions and electrical energy to the coefficient of performance (COP) of an air-source

Abstract

Purpose

The purpose of this study was to build and develop mathematical models correlating ambient conditions and electrical energy to the coefficient of performance (COP) of an air-source heat pump (ASHP) water heater. This study also aimed to design a simulation application to compute the COP under different heating up scenarios, and to calculate the mean significant difference under the specified scenarios by using a statistical method.

Design/methodology/approach

A data acquisition system was designed with respect to the required sensors and data loggers on the basis of the experimental setup. The two critical scenarios (with hot water draws and without hot water draws) during the heating up cycles were analyzed. Both mathematical models and the simulation application were developed using the analyzed data.

Findings

The predictors showed a direct linear relationship to the COP under the no successive hot water draws scenario, while they exhibited a linear relationship with a negative gradient to the COP under the simultaneous draws scenario. Both scenarios showed the ambient conditions to be the primary factor, and the weight of importance of the contribution to the COP was five times more in the scenario of simultaneous hot water draws than in the other scenario. The average COP of the ASHP water heater was better during a heating cycle with simultaneous hot water draws but demonstrated no mean significant difference from the other scenario.

Research limitations/implications

There was a need to include other prediction parameters such as air speed, difference in condenser temperature and difference in compressor temperature, which could help improve model accuracy. However, these were excluded because of insufficient funding for the purchase of additional temperature sensors and an air speed transducer.

Practical implications

The research was conducted in a normal middle-income family home, and all the results were obtained from the collected data from the data acquisition system. Moreover, the experiment was very feasible because the conduction of the study did not interfere with the activities of the house, as occupants were able to carry out their activities as usual.

Social implications

This paper attempts to justify the system efficiency under different heating up scenarios. Based on the mathematical model, the performance of the system could be determined all year round and the payback period could be easily evaluated. Finally, from the study, homeowners could see the value of the efficiency of the technology, as they could easily compute its performance on the basis of the ambient conditions at their location.

Originality/value

This is the first research on the mathematical modeling of the COP of an ASHP water heater using ambient conditions and electrical energy as the predictors and by using surface fitting multi-linear regression. Further, the novelty is the design of the simulation application for a Simulink environment to compute the performance from real-time data.

Article
Publication date: 17 October 2018

Stephen Loh Tangwe and Michael Simon

The purpose of this paper is fourfold: to experimentally determine the standby thermal energy losses in various hot water cylinders in both scenarios, without isotherm blanket…

Abstract

Purpose

The purpose of this paper is fourfold: to experimentally determine the standby thermal energy losses in various hot water cylinders in both scenarios, without isotherm blanket installation and with isotherm blanket installation; to analytically evaluate the performance of either the geyser, split- or integrated-type ASHP water heaters based on the number of heating up cycles and total electrical energy consumptions over a 24-h period without isotherm blankets and with isotherm blankets installed; to demonstrate the impact of the electrical energy factors of the split- and integrated-type ASHP water heaters under both the scenarios (without and with the isotherm blankets installed); and to use statistical tests (one way ANOVA and multiple comparison procedure tests) to verify whether any significant difference in the standby thermal energy losses occurred for each of the heating devices under both the scenarios.

Design/methodology/approach

The methodology was divided into monitoring of the performance of the electrical energy consumptions and ambient conditions of the hot water heating technologies without isotherm blanket installation and with isotherm blanket installation.

Findings

The results reveal that the average standby thermal energy loss of the geyser without the installation of an isotherm blanket was 2.5 kWh. And this standby loss can be reduced to over 18.5 per cent by just installing a 40-mm thick isotherm blanket on the tank. The statistical tests show a significant mean difference in the group electrical energy consumed to compensate for the standby losses under both scenarios. In contrast, the average standby thermal energy losses for the split- and integrated-type ASHP water heaters were 1.33 kWh and 0.92 kWh, respectively. There was a reduction of 15.5 per cent and 3.5 per cent in the electrical energy consumed in compensating for standby losses for both the split and integrated types, respectively, but there was no significant mean difference in the standby losses under both scenarios for the two systems. Again, without any loss of generality, the electrical energy factor of both the ASHP water heaters decreased upon installation of the isotherm blanks.

Research limitations/implications

The experiments were conducted only for a 150-L geyser and 150-L split- and integrated-type ASHP water heaters. The category of the different types of ASHP water heaters was limited to one because of the cost implication.

Practical implications

The experiments were not conducted with various hot water storage tanks installed in different positions (roof, inside or outside of a building wall, etc.) so that actual real-life observations could be obtained. The challenges of easy disassembling and deployment of systems and DAS to different positions were also a real concern.

Social implications

The findings can help homeowners and ESCO in deciding whether to install isotherm blankets on storage tanks of ASHP water heaters on the basis of the impact of standby losses and its potential viability.

Originality/value

The experimental design and methodology are the first of its kind to be conducted in South Africa. The results and interpretation were obtained from original data collected from a set of experiments conducted. The findings also show that the installation of isotherm blanket on an electric geyser can result in a significant mean reduction in the standby losses. In contrast, an installation of the isotherm blankets on the storage tanks of ASHP water heaters can reduce the standby losses, but there exists no significant mean difference.

Details

Journal of Engineering, Design and Technology, vol. 16 no. 5
Type: Research Article
ISSN: 1726-0531

Keywords

Article
Publication date: 12 January 2010

Wei Pan

The UK Government's housing agenda, coupled with the current market conditions, has provided the housebuilding industry with a challenge to build more new homes while improving…

2505

Abstract

Purpose

The UK Government's housing agenda, coupled with the current market conditions, has provided the housebuilding industry with a challenge to build more new homes while improving business efficiency to survive. Although innovation has been claimed as the key to meeting the challenge, the level of its usage has been reported low. This paper aims to reveal an insight into the success, inertia and failure of innovations and improve innovation management for housebuilding firms.

Design/methodology/approach

The paper reports on a two‐year case study of a large UK housebuilding company. It investigates the lifecycle of two product innovations, i.e. photovoltaic and air source heat pumps, and two process innovations, i.e. development efficiency plan and glossary of terms.

Findings

Five key stages of managing innovation are identified which represent the thematic consistency among the innovation processes, i.e. the creation of ideas, development of innovation, utilisation, review and improvement or abandonment. The organisational construct of the company for managing innovation is complicated and appeared difficult to manipulate, which constitutes a cultural and administrative obstacle. Whilst the adoption of the innovations from the market seems more straightforward than those created and developed in the company, the success or failure of innovation is driven by the combination of external and internal contextual issues. Strategies are developed which should improve the effectiveness of managing innovation in housebuilding and contribute to relevant future debate.

Originality/value

The paper provides insight into managing innovation in UK housebuilding.

Details

Engineering, Construction and Architectural Management, vol. 17 no. 1
Type: Research Article
ISSN: 0969-9988

Keywords

Article
Publication date: 28 October 2014

Rajat Gupta and Laura Barnfield

This paper aims to, using a systematic mixed-methods based monitoring and evaluation approach, investigate the unintended consequences of physical and technical home improvements…

1955

Abstract

Purpose

This paper aims to, using a systematic mixed-methods based monitoring and evaluation approach, investigate the unintended consequences of physical and technical home improvements on energy use, indoor environmental conditions and occupant behaviour in community-led retrofits. The study is part of a UK Research Council funded research project on evaluating the impacts and effectiveness of low carbon communities on energy behaviours.

Design/methodology/approach

A graduated measurement, monitoring and evaluation framework has been developed and applied to gather quantitative and qualitative data on energy use and behaviours has been developed and applied to 88 households across the UK. A mixed-methods approach is used, including occupant interviews, questionnaires, activity diaries and continuous physical monitoring of energy use, environmental conditions and low-carbon technologies.

Findings

The study has uncovered a number of unintended consequences associated with home energy improvements, both beneficial and detrimental, including improved comfort levels in retrofitted dwellings and reduction in energy use but also an increased likelihood of overheating following fabric improvements, potential under-performance of low-carbon systems due to lack of understanding and inadequate installation and commissioning, along with adaptive energy behaviours leading to increased energy use and a widening gap between predicted and actual savings.

Research limitations/implications

Although 63 case study households are involved, it is difficult to provide statistical analysis from the emerging findings.

Practical implications

This paper demonstrates the unintended consequences of home energy improvements. It aims to bring awareness of these issues to various sectors and stakeholders involved in delivering community retrofit programmes or the National Green Deal programme.

Originality/value

The paper fulfils an identified need to study the impacts of home energy improvements within existing homes through a robust, comprehensive M&E approach.

Article
Publication date: 21 November 2023

Nimasha Dilukshi Hulathdoowage, Gayani Karunasena, Nilupa Udawatta and Chunlu Liu

Over the years, the significance of retrofitting has gained much attention with the unveiling of its different applications, such as energy retrofit and deep retrofit, to enhance…

Abstract

Purpose

Over the years, the significance of retrofitting has gained much attention with the unveiling of its different applications, such as energy retrofit and deep retrofit, to enhance the climate-resilience of buildings. However, no single study comprehensively assesses the climate-resilience of retrofitting. The purpose of this study is to address this gap via a systematic literature review.

Design/methodology/approach

Quality journal studies were selected using the PRISMA method and analysed manually and using scientometrics. Three dimensions of climate-resilience, such as robustness, withstanding and recovery, were used to evaluate the contribution of retrofit measures for achieving climate-resilient houses across four climate zones: tropical, arid, temperate and cold.

Findings

Most passive measures can enhance the robustness of residential buildings but cannot verify for withstanding against immediate shocks and timely recovery. However, some passive measures, such as night-time ventilation, show excellent performance over all four climate zones. Active measures such as heating, ventilation and air conditioning and mechanical ventilation with heat recovery, can ensure climate-resilience in all three dimensions in the short-term but contribute to greenhouse gas emissions, further exacerbating the long-term climate. Integrating renewable energy sources can defeat this issue. Thus, all three retrofit strategies should appropriately be adopted together to achieve climate-resilient houses.

Research limitations/implications

Since the research is limited to secondary data, retrofit measures recommended in this research should be further investigated before application.

Originality/value

This review contributes to the knowledge domain of retrofitting by assessing the contribution of different retrofit measures to climate-resilience.

Details

International Journal of Disaster Resilience in the Built Environment, vol. ahead-of-print no. ahead-of-print
Type: Research Article
ISSN: 1759-5908

Keywords

Article
Publication date: 26 October 2021

Ina Eileen Peukes, Pomponi Francesco and Bernardino D'Amico

Operational energy use in buildings accounts for 28% of global energy demand. One method to reduce operational energy is upgrading old appliances to more efficient ones. In…

Abstract

Purpose

Operational energy use in buildings accounts for 28% of global energy demand. One method to reduce operational energy is upgrading old appliances to more efficient ones. In Australia, the most common residential heating type is reverse-cycle heating, followed by gas heating. This article aims to determine the energy balance resulting from a gas heating upgrade through a life cycle assessment (LCA).

Design/methodology/approach

Extensive primary data were collected for operational energy performance of 61 ducted gas heating upgrades. To address the scarcity of data on material composition, one ducted gas heater was deconstructed and assessed in terms of material composition (types and weights). The comparison between embodied energy and operational energy savings allows us to establish whether operational energy savings offset the embodied energy incurred with the upgrade. The end of life stage of the old appliance, as well as the production, construction and use stage of the new appliance were assessed.

Findings

The results show that the operational energy savings offset the following impact categories: global warming, ozone layer depletion, aquatic acidification, nonrenewable energy and carcinogens. Only the mineral extraction is not offset by the operational energy savings. The results clearly demonstrate that operational energy savings outweigh the embodied energy and therefore contribute positively to the environment.

Originality/value

This study is the first to focus on the LCA of building services through extensive primary data collection and a focus on a high number of appliances. This supports ongoing energy efficient upgrades in Australia and paves the way for further, similar studies to confirm or disprove these findings in other parts of the world.

Details

International Journal of Building Pathology and Adaptation, vol. 41 no. 1
Type: Research Article
ISSN: 2398-4708

Keywords

Article
Publication date: 24 October 2021

Anges Akim Aminou Moussavou, Ayokunle Oluwaseun Ayeleso, Marco Adonis and Atanda Raji

This paper aims to develop a selective energy optimisation of the photovoltaic–thermal (PV/T) system performance. The PV cell inside the PV/T system could be periodically…

Abstract

Purpose

This paper aims to develop a selective energy optimisation of the photovoltaic–thermal (PV/T) system performance. The PV cell inside the PV/T system could be periodically manipulated to produce domestic hot water without applying an external power supply.

Design/methodology/approach

A numerical simulation model of the proposed PV/T model was developed in MATLAB/Simulink to analyse the selective energy optimisation of the model. The extrinsic cell resistance (Rse) is adjusted to control the ratio of thermal to the electrical energy, generated from the PV cell inside the PV/T system. Therefore, the internal heat of the PV cell inside the PV/T system is periodically used as a thermal element to produce electrical power and hot water.

Findings

The optimisation of PV/T energy shows that the electrical power efficiency can increase by 11.6% when Rse was 0 Ω, and the 200 L water tank temperature increased by 22ºC when Rse was 50 Ω.

Originality/value

This study showed that the use of the PV cell could be extended to domestic hot water and space heating, and not only for electricity.

Details

Journal of Engineering, Design and Technology , vol. 21 no. 5
Type: Research Article
ISSN: 1726-0531

Keywords

Article
Publication date: 26 August 2014

Wai Ming To, Hon Kit Hung and Wai Leung Chung

The purpose of this paper is to evaluate the energy, economic and environmental performance of commercial water heating systems in Hong Kong special administrative region (SAR)…

Abstract

Purpose

The purpose of this paper is to evaluate the energy, economic and environmental performance of commercial water heating systems in Hong Kong special administrative region (SAR), China.

Design/methodology/approach

The research team contacted 50 facilities managers in Hong Kong, and 16 of them agreed to participate in this territorial-wide survey. The overall efficiency of different water heating systems was determined through measurements of inlet water temperatures, outlet steam/water properties, the amount of steam/water produced and the amount of energy consumed. The cost effectiveness and the amount of greenhouse gases produced per megajoule (MJ) output were also determined.

Findings

Results show that electric water heating systems had the highest mean overall efficiency, followed by gas- and oil-fired systems. However, the difference between the mean overall efficiency of the three types of water heating systems was not statistically significant, as the systems had been inspected and maintained regularly. Oil-fired systems were found to be the most cost-effective when taking fuel prices into consideration. Environmental analysis showed that gas-fired systems produced the least amount of greenhouse gases per MJ output.

Originality/value

Water heating is one of the major uses of energy in buildings. Hence, the efficiency of a water heating system can have a significant effect on the overall performance of a building. This paper not only provides insight on the energy performance but it also evaluates the economic and environmental performance of water heating systems.

Details

Journal of Facilities Management, vol. 12 no. 4
Type: Research Article
ISSN: 1472-5967

Keywords