To read this content please select one of the options below:

Safety lighting: exterior illumination at an existing US government facility

Paulette Hebert (Department of Design, Housing and Merchandising, Oklahoma State University, Stillwater, Oklahoma, USA)
Mihyun Kang (Department of Design, Housing and Merchandising, Oklahoma State University, Stillwater, Oklahoma, USA)
Jessy Kramp (Department of Design, Housing and Merchandising, Oklahoma State University, Stillwater, Oklahoma, USA)

Journal of Facilities Management

ISSN: 1472-5967

Article publication date: 4 July 2013

551

Abstract

Purpose

The purpose of this paper is to examine safety lighting at an existing US government facility.

Design/methodology/approach

Field measurements of exterior illumination were conducted at four building sites housing laboratories, offices and a cafeteria at night and the findings were compared to the industry recommendations, the Illuminating Engineering Society of North America (IES) safety lighting recommendations.

Findings

Laboratory, office and cafeteria building exteriors were classified as “high hazard” due to area wildlife, potentially dangerous equipment and chemicals, the threat of intruders, and uneven terrain. Some sites' existing light levels fell far below industry recommendations and others greatly exceeded recommendations. Most of the existing lighting was uneven, unsustainable, rendered colors poorly, produced glare and/or remained energized when no one was present.

Research limitations/implications

This study is limited by the small number of sites and limited geographical area of the sites. Lighting field studies can improve user safety, save energy and reduce facilities' waste.

Practical implications

This study employs a relatively simple approach to examine safety lighting that facility managers could adapt for their own facilities to inform improvements.

Originality/value

The current lack of lighting field studies, safety lighting research and case studies regarding government facilities is addressed by contributions of this research.

Keywords

Citation

Hebert, P., Kang, M. and Kramp, J. (2013), "Safety lighting: exterior illumination at an existing US government facility", Journal of Facilities Management, Vol. 11 No. 3, pp. 210-225. https://doi.org/10.1108/JFM-07-2012-0032

Publisher

:

Emerald Group Publishing Limited

Copyright © 2013, Emerald Group Publishing Limited

Related articles