Nonlinear secondary arc model use for evaluation of single pole auto-reclosing effectiveness

Jacek Klucznik (Faculty of Electrical and Control Engineering, Gdansk University of Technology, Gdansk, Poland)
Zbigniew Lubosny (Faculty of Electrical and Control Engineering, Gdansk University of Technology, Gdansk, Poland)
Krzysztof Dobrzynski (Faculty of Electrical and Control Engineering, Gdansk University of Technology, Gdansk, Poland)
Stanislaw Czapp (Faculty of Electrical and Control Engineering, Gdansk University of Technology, Gdansk, Poland)

Abstract

Purpose

The purpose of this paper is to discuss two evaluation methods of single pole auto-reclosing process effectiveness in HV transmission lines. Secondary arc current and recovery voltage results obtained by load flow calculation are compared to the results obtained by the time domain simulations. Moreover, a nonlinear secondary arc implementation is presented.

Design/methodology/approach

A computer simulation studies were performed using DIgSILENT PowerFactory® software to analyse phenomena during single phase to earth short circuit and during single pole circuit breaker opening. Possibilities of electric arc extinction for different earthing solutions of shunt reactors were examined.

Findings

The authors indicate, that precise representation of secondary electric arc in power system studies could lead to different conclusion than analysis carried out on simplified arc models. Recommendations for line construction (i.e. earthing reactor installation) and line operation (i.e. prolongation of dead time during auto-reclosing) based on time domain simulations are less restrictive than resulting from the traditional steady-state calculation approach.

Originality/value

An implementation of mathematical model of nonlinear secondary arc for DIgSILENT PowerFactory® software is presented. The model could be used during the process of design of HV transmission line, to assess its proper operation, to calculate dead time during single pole reclosing or to evaluate the necessity of installing additional earthing reactors.

Keywords

Citation

Klucznik, J., Lubosny, Z., Dobrzynski, K. and Czapp, S. (2015), "Nonlinear secondary arc model use for evaluation of single pole auto-reclosing effectiveness", COMPEL - The international journal for computation and mathematics in electrical and electronic engineering, Vol. 34 No. 3, pp. 647-656. https://doi.org/10.1108/COMPEL-10-2014-0252

Publisher

:

Emerald Group Publishing Limited

Copyright © 2015, Emerald Group Publishing Limited

Related articles