To read this content please select one of the options below:

Automatic fault detection for Building Integrated Photovoltaic (BIPV) systems using time series methods

Mohsen Shahandashti (University of Texas at Arlington, Arlington, Texas, USA)
Baabak Ashuri (Economics of the Sustainable Built Environment (ESBE) Lab, School of Building Construction, Georgia Institute of Technology, Atlanta, Georgia, USA)
Kia Mostaan (Cambridge Systematics, Cambridge, Massachusetts, USA)

Built Environment Project and Asset Management

ISSN: 2044-124X

Article publication date: 13 April 2018

Issue publication date: 10 May 2018

125

Abstract

Purpose

Faults in the actual outdoor performance of Building Integrated Photovoltaic (BIPV) systems can go unnoticed for several months since the energy productions are subject to significant variations that could mask faulty behaviors. Even large BIPV energy deficits could be hard to detect. The purpose of this paper is to develop a cost-effective approach to automatically detect faults in the energy productions of BIPV systems using historical BIPV energy productions as the only source of information that is typically collected in all BIPV systems.

Design/methodology/approach

Energy productions of BIPV systems are time series in nature. Therefore, time series methods are used to automatically detect two categories of faults (outliers and structure changes) in the monthly energy productions of BIPV systems. The research methodology consists of the automatic detection of outliers in energy productions, and automatic detection of structure changes in energy productions.

Findings

The proposed approach is applied to detect faults in the monthly energy productions of 89 BIPV systems. The results confirm that outliers and structure changes can be automatically detected in the monthly energy productions of BIPV systems using time series methods in presence of short-term variations, monthly seasonality, and long-term degradation in performance.

Originality/value

Unlike existing methods, the proposed approach does not require performance ratio calculation, operating condition data, such as solar irradiation, or the output of neighboring BIPV systems. It only uses the historical information about the BIPV energy productions to distinguish between faults and other time series properties including seasonality, short-term variations, and degradation trends.

Keywords

Acknowledgements

This material is based upon work supported by the National Science Foundation under Grants No. 1300918 and 1441208.

Citation

Shahandashti, M., Ashuri, B. and Mostaan, K. (2018), "Automatic fault detection for Building Integrated Photovoltaic (BIPV) systems using time series methods", Built Environment Project and Asset Management, Vol. 8 No. 2, pp. 160-170. https://doi.org/10.1108/BEPAM-07-2017-0045

Publisher

:

Emerald Publishing Limited

Copyright © 2018, Emerald Publishing Limited

Related articles