To read this content please select one of the options below:

Failure of a control strategy for a hybrid air‐conditioning and wind catchers/towers system at Bluewater shopping malls in Kent, UK

Abbas Ali Elmualim (The School of Construction Management and Engineering, Innovative Construction Research Centre, The University of Reading, Reading, UK)

Facilities

ISSN: 0263-2772

Article publication date: 1 September 2006

1294

Abstract

Purpose

To evaluate the control strategy for a hybrid natural ventilation wind catchers and air‐conditioning system and to assess the contribution of wind catchers to indoor air environments and energy savings if any.

Design/methodology/approach

Most of the modeling techniques for assessing wind catchers performance are theoretical. Post‐occupancy evaluation studies of buildings will provide an insight into the operation of these building components and help to inform facilities managers. A case study for POE was presented in this paper.

Findings

The monitoring of the summer and winter month operations showed that the indoor air quality parameters were kept within the design target range. The design control strategy failed to record data regarding the operation, opening time and position of wind catchers system. Though the implemented control strategy was working effectively in monitoring the operation of mechanical ventilation systems, i.e. AHU, did not integrate the wind catchers with the mechanical ventilation system.

Research limitations/implications

Owing to short‐falls in the control strategy implemented in this project, it was found difficult to quantify and verify the contribution of the wind catchers to the internal conditions and, hence, energy savings.

Practical implications

Controlling the operation of the wind catchers via the AHU will lead to isolation of the wind catchers in the event of malfunctioning of the AHU. Wind catchers will contribute to the ventilation of space, particularly in the summer months.

Originality/value

This paper demonstrates the value of POE as indispensable tool for FM professionals. It further provides insight into the application of natural ventilation systems in building for healthier indoor environments at lower energy cost. The design of the control strategy for natural ventilation and air‐conditioning should be considered at the design stage involving the FM personnel.

Keywords

Citation

Elmualim, A.A. (2006), "Failure of a control strategy for a hybrid air‐conditioning and wind catchers/towers system at Bluewater shopping malls in Kent, UK", Facilities, Vol. 24 No. 11/12, pp. 399-411. https://doi.org/10.1108/02632770610684882

Publisher

:

Emerald Group Publishing Limited

Copyright © 2006, Emerald Group Publishing Limited

Related articles